Sweep Frequency Response Analyzer SFRA20

Adopting frequency-sweep method to measure transformer winding characteristics.

Deformations of windings such as distortion, swell or displacement of transformer measured by detecting amplitude-frequency response characteristics of each winding, not requiring lifting of transformer enclosure or disintegration.

Quick measuring, measuring of a single winding is within 2 minutes.

High frequency accuracy, higher than 0.001%.


Features

Technical Index

Adopting frequency-sweep method to measure transformer winding characteristics.

Deformations of windings such as distortion, swell or displacement of transformer measured by detecting amplitude-frequency response characteristics of each winding, not requiring lifting of transformer enclosure or disintegration.

Quick measuring, measuring of a single winding is within 2 minutes.

High frequency accuracy, higher than 0.001%.

Digital frequency synthesis, with higher frequency stability.

5000V voltage isolation fully protects safety of the testing computer.

Able to load 9 curves at the same time and automatically calculate parameters of each curve and diagnose winding deformations to provide the reference diagnosis conclusion.

Analysis software has powerful functions and software and hardware indicators.

Software management is humanized with high degree of intelligence. You only need to click a key to complete all measurements after setting of parameters.

The software interface is concise and vivid, with clear menus of analysis, save, report export, print, etc. 


  • Previous:
  • Next:

  • Item Specification
    Measuring speed 1 min- 2 min for single-phase winding
    Output voltage Vpp-25V, adjusting automatically in test
    Output impedance 50Ω
    Input impedance 1MΩ (the response channel is built with 50Ω matching resistance)
    Frequency scan scope 10Hz-20MHz
    Frequency accuracy 0.001%
    Frequency scan manner linear or logarithmic, frequency scan interval and number of sweep points are freely settable
    Curve display amplitude-frequency curve (phase-frequency curve, optional)
    Width of measuring dynamic range -120dB~20dB
    Supply voltage AC100-240V   50/60Hz  (use DC12V Adapater recommend)
    Dimension   238mm*184mm*40mm
    Net  weight 2.45Kg