Protection Relay Test Kit MCRT66

LCD display.

AC/DC maximum output voltage: 6*150V, 3*300V, 1*900V.

AC/DC maximum output current: 6*35A, 3*70A, 1*180A.

Output accuracy: 0.2%.

In-built computer.

Also can be operated by external PC.

Transient playback/Vector display.

RIO/XRIO file import/export (optional).

Optional for Energy meter test/IEC61850 goose/Transducer test/GPRS.


Features

Technical Index

High power & high reliability switch amplifier.

Adopt DSP technology.

High Output Accuracy.

Self-protection function.

Modularization Design & Mutual independent between all comprising Parts, between amplifier boards.

Graphical test modules and templates for testing of various relays.

Energy meter test  (optional).

Transducer Test (optional).

GPRS sync end-to-end testing (optional).

Big LCD and in-built computer.

Transient Playback.

Vector display.

Automatic test results assume.

Automatically create test report.

Wrong wiring alarm and, overload and overheat protection.

Interface: Ethernet port for PC connection; IEC61850.

Operated by in-built computer or by PC.


  • Previous:
  • Next:

  • AC voltage source MAX output voltage 6×150V , 3×300V , 1×900V
    MAX output power 6×75VA or 3×150VA
    resolution 5mV
    Accuracy ≤0.2%
    Harmonic distortion ≤0.2%
    Other Output amplitude/frequency/phase of each phase can be adjustable independently, and with short circuit protection and over current protection
    AC current source MAX output current 6×35A , 3×70A , 1×180A
    MAX output power 6×300VA, 3×600VA , 1×1800VA
    resolution 1mA
    Accuracy ≤0.2%
    Harmonic distortion ≤0.2%
    Other Output amplitude/frequency/phase of each phase can be adjustable independently, and with open circuit protection and over load protection
    DC Voltage MAX output voltage 6×150V , 3×300V , 1×900V 
    MAX output power 6×75W ,3×150W
    Accuracy ≤0.2%
    Other Short circuit,over-current protection
    DC current MAX output current 6×35A , 3×70A , 1×180A
    MAX output power 6×300W , 3×600W , 1×1800W
    Accuracy ≤0.2%
    Other Open circuit, over-load protection
    AUX DC voltage Output 0~250V continuously adjustable;  Fast switch between 24、110V、220V;Output Power:120W
    other Short circuit,over-load protection
    Phase range -360°~ +360°
    accuracy 0.01°
    frequency range DC 10~1000Hz
    resolution 0.001Hz
    drifting 5ppm
    Binary input  Quantities 8 pairs
    Response time 50μs
    timing range 1ms~999,999.999s
    Input way Idle contact or Potential automatic identification,withstand voltage  250V
    Other Auti-shake time adjustable
    Binary output  Quantities 4 pairs
    Output way Idle contact, withstand voltage  250V ,capacity 250VA
    DC measurement (transducer calibration) Voltage one group, input±10V, accuracy  <0.05%
    Current one group, input ±20mA,accuracy  <0.05%
    impulse Max receivable frequency  30KHz
    Energy Meter Calibration Type of meter under test Electromechanical & Electronic
    Pulse Range Maximum frequency 2MHZ
    Test Function Error test
    Configuration 1 No optical sensor
    Key board In-built 24 keys
    external PS/2 port
    Display screen size 8.4 “
    resolution 800×600
    color TFT
    Touching screen LCD 8.4“
    Mouse PS/2 port
    USB port One , USB2.0
    Web port one
    size 471mm×192mm×363mm
    weight 18.7 kgs
    Power Supply Single phase AC 90-260V, 50/60HZ, 3KW/15A