Protection Relay Test Kit MCRT43

4U+3I source.

Used in lab or worksite.

LCD display.

AC output Range: 3*(0-40A)/4*(0-120V).

DC output Range: 0-±160V/0-±10A per phase.

Output accuracy: 0.2%.

With in-built computer, and also can be operated by external PC.

Fault playback.


Features

Technical Index


  • Previous:
  • Next:

  • AC current source
    Output accuracy 0.2%
    Output range 3*(0-40A); 0-120A (three phases in parallel)
    Phase current which can get long-time working 10A
    Maximum output power of phase current: 420VA
    Maximum output power of three phase current in parallel: 900VA
    Permissible working time (when three phase current in parallel to get maximum output): 10s
    Frequency (basic wave) range 20-1000Hz
    Harmonics times 1-20 times
    DC current source
    Output accuracy 0.2%
    Current output 0-+/-10A per phase; 0-+/-30A (three phase in parallel)
    Maximum load voltage output 20V
    AC voltage source
    Output accuracy 0.2%
    Phase voltage output 4*(0-120V)
    Line voltage output 0-240V
    Phase voltage/line voltage output power 80VA/100VA
    Frequency (basic wave) range 20-1000Hz
    Harmonics 1-20 times
    DC voltage source
    Output accuracy 0.2%
    Phase voltage output amplitude 0-+/-160V
    Line voltage output amplitude 0-+/-320V
    Phase voltage/line voltage output power  70VA/140VA
    Dimension 400*300*180mm
    Weight  approx 18KG
    Power supply AC 220V±10%,50/60Hz
    Ambient temperature -10℃~ +50℃

    Switch signal and time measurement

    Switch signal input

     

    10circuits

    Idle contact: 1~20mA,24VPotential contact access: “0”:0~ +6V; “1”:+11 V~ +250V

    Switch signal output

    8 pairs

    DC:220V/0.2A;AC:220V/0.5A

    Time measure

    Test range: 0.1ms ~ 9999s , accuracy 0.1mSMeasurement range: 0.1ms ~ 9999sMeasurement accuracy:0.1mS