Portable Electronic (Digital) CT/VT Calibrator HEWD-2A
Primary rated voltage measure | up to 500KV |
Primary rated current measure | 5-5000A, customization available |
Standard signal input | |
Voltage input | 0-120%Un, Un=100V、100/√3V. Customization available |
Current input | 0-120%In, In=1A or 5A. Customization available |
Analog input signal | 0-10V (peak value) |
Small signal (sine wave) output | 0-4V (RMS value) |
Accuracy class | |
Ratio error | <0.05% (1-120% rated value) |
Phase error | <2´(1-120% rated value) |
Absolute delay | <1µS (waveform distortion less than 1%) |
Delay jitter | <0.5µS |
ST optical fiber interface (one group) | |
Optical fiber Transmitting Power | >-6dBm |
Optical Receiving sensitivity | -38dBm |
Sync signal | |
Optical PPS sync input & output | 4Nos |
Optical IRIG-B(DC) sync input & output | 4Nos |
Sync output time accuracy | better than 100ns |
Input supply | AC220V±10%, 50/60HZ, power consumption less than 20W |
Working condition | temperature 0℃~+40℃/Humidity ≤85% |
Size & Weight | 360*400*160mm/7.5kgs |