MCVT405 CT/PT Analyzer
1) Test standards: IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
2) Power supply: AC220V±10%, 50/60Hz±10%
3) Voltage/Current output: 0.1~180V (AC) / 0.001~5A(RMS)
5) Power output: 500VA
6) Maximum knee voltage measurement: 45KV
7) Current measurement
Range: 0~10A (automatically change range in 0.1/0.4/2/10A)
Error: <±0.1%+0.01%FS
8) Voltage measurement
Range: 0~200V (automatically change range in 1V/10V/70V/200V)
Error: < ±0.1%+0.01%FS
9) Turns ratio measurement & error
Range: 1~35000
1~5000 (error<0.05%) & 5000~35000 (error<0.1%)
10) Phase measurement error: ±2min & resolution: 0.01min
11) Winding resistance measurement
Range: 0~8kΩ (automatically change range in 2ohm/20ohm/80ohm/800ohm/8kohm)
Error: < 0.2%RDG+0.02%FS
Maximum resolution: 0.1mΩ
12) Temperature measurement:-50~100 Celsius degree; error<3 Celsius degree
13) CT Secondary burden
Range: 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error: <0.2%RDG+0.02%FS
Maximum resolution: 0.001ohm
14) PT Secondary burden
Range: 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Error :<0.2%RDG+0.02%FS
Maximum resolution: 0.1ohm
15) PT ratio measurement & error
Range: 1~35000
1~10000 (error<0.1%) & 10000~35000 (error<0.2%)
16) PT ratio error measurement: Typical error <0.05%, Maximum Error<0.1%
17) PT phase angle measurement: maximum error < 3min
18) Make evaluation for test results according to selected standards
19) Make word report for test result
20) Make word reports one time for multi-group test records on the PC
21) Calculate ratio errors and phase angle errors at rated burden and working burden in one time test
22) Compare excitation curves with saved excitation curves in the same window
23) Memory capacity: >1000 groups test results
24)Working condition: temperature: -10℃~50℃; moist: ≤90%
25) Size: 485mm×356mm×183mm
26) Weight: <15kg