Portable Three Phase Meter Test System MCPTS4.0

1.Error test, start test, creep test, dial test, CT ratio error test, CT phase angle error test, CT/PT burden test

 

2.Can be independent set & output of each phase voltage & current

 

3.Can be independently used as portable reference meter

 

4.External connect with thermal printer (optional)

 

5.Can operate by PC software

 

6.Manual control by touch screen/keypad


Features

Technical Index

Features

1)7”LCD display

2)In-built standard meter class 0.05 and compact current & voltage source

3)Impulse input and output

4)Independently use as below:

-Current and voltage source (Available to connect one external standard meter for calibration)

-Portable Reference Standard Meter (Available to connect one external current & voltage source for calibration, and also can use clamp-on CTs)

-Portable Meter Test Equipment (Reference standard and integrated current and voltage source)

5)Test of various single phase and three phase electromechanical /electronic energy meter

6)Automatic operation with predefined load points without need for external PC

7)Test and display voltage, current, phase, error, active energy, reactive energy, apparent energy, power, phase angle, power factor, frequency and etc

8)Display vector diagram, harmonic spectrum and waveform

9)In-built error calculator to calculate error of meter under test

10)Enough protection, like short-circuit voltage, current open-circuit protection, overload protection, over-voltage protection

11)2-51 times harmonics test/Dial test/Start test/Creep test

12)CT ratio error Test/CT phase angle error test/CT burden Test/PT burden Test (optional)

13)RS232 communication port and Software Control by PC

14)Test records data can be uploaded to computer by RS232 or USB port

15)External connect with blue-tooth mini printer for printing test result (optional)

Voltage Source

Voltage Range:   30-480V (P-N) Per phase

Resolution:   0.001 - 0.0001V

Output Accuracy:   0.05%

Output capacity:  30VA/phase

Distortion Factor:   ≤0.2%

Output Stability:   0.03%/30min

Load Regulation (0-100% load):   0.01%

Current Source

Current range:   1mA –20A (Range depends on client, can be maximum 120A),

Resolution:  0.0001 - 0.00001A

Output Accuracy:    0.05%

Output capacity:  60VA/Phase

Distortion Factor:    ≤0.2%

Output Stability:     0.02% / 3min

Load Regulation (0-100% load):  0.02%

Generation Of Harmonics

Fundamental Frequency Range:  45-69HZ

Harmonics test:    2-31times

Sum of Harmonics Content of harmonics
2-8 times 40%
9-15times 30%
16-31times 20%

Phase shift (basic Waveform/Harmonic):   0-360°

Configuration & Accessories List

Item Quantity
Main unit 1
Test Rack (3 position) 1
Voltage cable 1 set
Current cable 1 set
Optical sensor 3 Nos
Communication cable 1
Power cord 1
User manual 1
PC software (CD) 1

  • Previous:
  • Next:

  • Accuracy class:  0.05, 0.02 class (optional)

    Voltage range: 30-480V (P-N)

    Current range:  1mA-120A

    Supply Voltage:    AC 88-265V, 50/60HZ,

    Input Power Consumption:  Max 500VA

    Ambient Temperature:   -10℃-45℃

    Influence of auxiliary Voltage:    ≤0.005% at 10% Variation

    Dimension (approx):     570*416*282mm (main unit)

    Weight:  approx 28kgs

    Frequency Range & Resolution:     45-69HZ, 0.001HZ

    Phase Angle Range & Resolution:    0-359.99°, 0.001°

    Phase angle Error:          0.03°

    Communication Interface:    RS232

  • Write your message here and send it to us